CATEGORY
Post Indicator UG Type UL FM G388
GALA Regulating System Gate Valves
Field Adjustment:
1. Remove the top section from the top of the Indicator Post assembly.
2. Cut the required length off the bottom of the Standpipe for the Ground Line to match up with
Standpipe Ground Line mark.
3. Set the "OPEN" and "SHUT" targets for the appropriate valve size.
4. Reattach the Top Section to the top of the Indicator Post assembly.
5. Design and dimensions are subject to change without notice
Material List
1 | 2 | Locking Wrench | ASTM A 126B |
2 | 1 | Operating Nut | ASTM B62 105 |
3 | 2 | Hex Nut Screw | ASTM 105 |
4 | 2 | Hex Nut | ASTIM 105 |
5 | 1 | Snap Ring | AISI 066 |
6 | 1 | Taget Carrier Nut | ASTM B62 |
7 | 4 | Taget | ASTM B108 |
8 | 4 | Hex Cap Screw | ASTM A105 |
9 | 2 | Window Glass | LEXAN-UM |
10 | 2 | Window Glass Gasket | PTFE |
11 | 4 | Hex Cap Screw | ASTM A105 |
12 | 4 | Hex Nut | ASTM A105 |
13 | 1 | Body | ASTM A536 |
14 | 6 | Hex Cap Screw | ASTM A105 |
15 | 6 | Hex Nut | ASTM A105 |
16 | 1 | Base Flange | ASTM A126B |
17 | 4 | Hex Cap Screw | ASTM A105 |
18 | 4 | Hex Nut | ASTM A105 |
19 | 1 | Crane Coupling | ASTM A536 |
20 | 1 | Cotter Pin | AISI 304 |
21 | 1 | Stand Pipe | ASTM A53 |
22 | 1 | Stem | AISI 1045 |
23 | 1 | Plug | AISI 304 |
24 | 1 | Cover | ASTM A126B |
25 | 1 | Cross Recessed Countersunk Head Screw | AISI 304 |
26 | 1 | Locking Nose | ASTM 307B |